Description
The E-guard NML (Long life) range is a gel design with an AGM separator (commonly referred to as Lead Crystal) and is designed for solar and alternative energy systems.
Typical Applications
- Solar Energy Systems.
- Wind Energy Systems.
- Power Utility.
- UPS/EPS.
Electrical Specification
Design floating Life @ 20°C
- 15 years.
Nominal Capacity @ 25°C
- 20 hour rate 11.62A to 1.75Vpc 232.4 Ah.
- 10 hour rate 22.67A to 1.75Vp 226.6 Ah.
Internal Resistance (Fully charged battery @ 25°C)
- 3.5 mΩ.
Max. Discharge Current @ 25°C
- 2200 A (5S).
Charge Methods (Constant voltage charge @ 25°C)
- Cycle Use: 14.7 ~ 14.9V Max.
- Current: 58A.
- Standby Use: 13.6 – 13.8V.
Operating Temperature Range
- Discharge: -15 ~ 50°C.
- Charge: 0 ~ 50°C.
- Storage: -15 ~ 50°C.
- Recommended Operating Temp: 15 ~ 25°C.
Self-Discharge
- 3% of capacity declined per month @ 20°C.
Dimensions and Weight
- L x W x H: 522mm x 269mm x 220mm
- Total Height: 225mm.
- Weight: 65.5Kg
Reviews